Power cabinet get electricity from ATS switch cabinet,mainly realize power supply for high-power air conditioning,lighting, maintenance in computer room,it is usually located in the back-end of ATS switch cabinet in data room, be used to distribute power to the the backend air conditioning, lighting boxes, refrigeration units, new fan,etc.
Power cabinet get electricity from ATS switch cabinet,mainly realize power supply for high-power air conditioning, lighting, maintenance in computer room, it is usually located in the back-end of ATS switch cabinet in data room, be used for distribute power to the the backend air conditioning, lighting boxes, refrigeration units, new fan, etc.
item | Parameters |
---|---|
Input capacity | Busbar/break line |
Cabinet size | 600/800/1000*800*2200 (WxDxH), according to the size of the ATS. |
Types of communication | RS485 |
Lightning protection level | Class C, 40kA(8/20μs) |
Maintenance mode | front and back sides maintenance |
Protection grade | IP20 |
input/output line mode | in and out from upside/in and out from downside |
installation mode | fixing on the floor |
Cooling way | Natural cooling |
certification | 3C certification, antiseismic grade 8, 9. |
output | Bus/plastic shell |
Monitoring parameters | Monitor input voltage, current, power, power factor, frequency and quantity of electric charge, equipped with 4.3 inch touch screen or panel type smart meter. |
Working temperature | Temperature 5 ℃ ~ + 40 ℃ |
Working humidity | 5%RH~95%RH |
The power supply system | 380/400/415V 50/60Hz |
Altitude | 0 ~ 2000m, limited using above 2000m. |